BACnet Protocol Implementation Conformance Statement

BACnet Protocol
|
Date: |
September 9, 2005 |
|
Vendor Name: |
FieldServer Technologies |
|
Product Name: |
FieldServer |
|
Product Model Number: |
FS-B4X, FS-B3X or FS-B2X Series, ProtoCessor FFP, SlotServer |
|
Product Descpription: |
This software product will provide bi-directional communication between various RTU, DCS, SCADA and PLC using most common protocols and a BACnet system. The FieldServer can do protocol conversion (as opposed to routing) between the different BACnent Data Link Layer options. This is arranged by way of static mappings. |
|
Protocol Conversions: |
See FieldServer Technologies list of protocols drivers available to determine what protocol conversions are available. |
BACnet Standardized Device Profile (Annex L) - [Note that the FieldServer is a gateway device]
| |
BACnet Smart Sensor | (B-SS) |
| |
BACnet Smart Actuator | (B-SA) |
BACnet Interoperability Building Blocks Supported (Annex K):
| K.1.1 BIBB - Data Sharing - ReadProperty-A | (DS-RP-A) | |
| |
K.1.2 BIBB - Data Sharing - ReadProperty-B | (DS-RP-B) |
| K.1.3 BIBB - Data Sharing - ReadPropertyMultiple-A (except ProtoCessor) | (DS-RPM-A) | |
| |
K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B (except ProtoCessor) | (DS-RPM-B) |
| |
K.1.7 BIBB - Data Sharing - WriteProperty-A | (DS-WP-A) |
| |
K.1.8 BIBB - Data Sharing - WriteProperty-B | (DS-WP-B) |
| K.1.12 BIBB - Data Sharing - COV-B | (DS-COV-B) | |
| K.2.2 BIBB - Alarm & Event-Notification Internal-B | (AE-N-I-B) | |
| K.5.1 BIBB - Device Management - Dynamic Device Binding-A | (DM-DDB-A) | |
| K.5.2 BIBB - Device Management - Dynamic Device Binding-B | (DM-DDB-B) | |
| |
K.5.3 BIBB - Device Management - Dynamic Device Binding-A | (DM-DOB-A) |
| |
K.5.4 BIBB - Device Management - Dynamic Device Binding-B | (DM-DOB-B) |
Segmentation Capability: None
|
Standard Object Types Supported |
|
|||||||||||||||||||||||||||
|
Object Type |
Supported |
|||||||||||||||||||||||||||
| Device Object | X | |||||||||||||||||||||||||||
| Analog Input | X | |||||||||||||||||||||||||||
| Analog Output | X | |||||||||||||||||||||||||||
| Analog Value | X | |||||||||||||||||||||||||||
| Binary Input | X | |||||||||||||||||||||||||||
| Binary Output | X | |||||||||||||||||||||||||||
| Binary Value | X | |||||||||||||||||||||||||||
| Multi State Input Object | X | |||||||||||||||||||||||||||
| Multi State Output | X | |||||||||||||||||||||||||||
| Multi State Value | X | |||||||||||||||||||||||||||
| Notification Class Object | X | |||||||||||||||||||||||||||
Data Link Layer Options:
| |
BACnet IP |
(Annex J) |
|
|
ISO 8802-3, Ethernet |
(Clause 7) |
| |
ANSI/ATA 878.1, 2.5 Mb, ARCNET |
(Clause 8) |
|
|
Point-to-Point, RS-232, baud rate up to 115 Kbps |
(Clause 10) |
MS/TP master, baud rate up to 114 Kbps |
(Clause 9) |
|
MS/TP slave, baud rate up to 115 Kbps |
(Clause 9) |
Device Address Binding:
|
Is static device binding supported? |
|
Yes |
No |
Networking Options:
| |
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. |
||||
|
|
Annex H, BACnet Tunneling Router over IP |
||||
| |
BACnet/IP Broadcast Management Device (BBMD) |
||||
|
Does the BBMD support registrations by Foreign Devices? |
|
Yes |
![]() |
No |
Character Sets Supported:
Indicate support for multiple sets does not imply that they can all be supported
simultaneously.
| |
ANSI X3.4 |
|
|
ISO 10646 (UCS-2) |
| |
IBM/Micosoft DBCS |
|
|
ISO 10646 (ICS-4) |
| |
ISO 8859-1 |
|
|
JIS C 6226 |
Unsupported functions of the BACnet Driver - BACnet/IP as a Client:
- Registering the FieldServer as a foreign device on a remote BBMD
- Configuring a Connection for BBMD operation.